The Truth about Valve Cv 's
Ask about our Compressed Air Savings Audit Services
Henry Fleischer - VP for Reasearch & Development Numatics, Inc.
Karl Foster - VP of Engineering Festo Corp.
David C. Franson - Tech. Service Manager Parker Hannifin Corp.
Most design engineers select pneumatic control valves based on performance data published by the valve manufacturer. Usually the key performance factor is how much air a particular valve can flow. When valves from different manufacturers are the same size and comparably priced, most designers naturally gravitate toward ones that offer the highest flow.
But when examining valve specifications, most potential buyers assume that every manufacturer's performance numbers are based on the same test method. In fact, this is not the case. Manufacturers in the Americas and Europe typically determine valve performance based on international test standards. Manufacturers in the Far East tend to use a different method and then apply conversion factors to present the data in a more widely accepted format.
Unfortunately, the lack of a universal test standard means users do not always get the performance they expect. Product catalog information on flow capacity can be inconsistent from one manufacturer to another and, if the difference is not recognized, it can create serious design difficulties.
Problems can arise, especially in close-tolerance applications that operate near a system's capacity limits. Cycle times can be slower than expected, since a valve's maximum flow may actually be lower than published figures would indicate. The result is an underperforming machine that may require costly redesign.
MEASURING FLOW
Pneumatic-valve flow represents a critical performance characteristic. To be meaningful, it must be determined by a standard, repeatable test method. Since 1989, this measurement has been defined by the international standard ISO 6358. National or branch standards-such as ANSI/NFPA T3.21.3-1990 in the U.S. and VDI 2173 in Germany-are based on this ISO standard.
The ISO 6358 test measures standard nominal flow qnN, which is converted to imperial flow coefficient Cv or metric equivalent Kv. Higher Cvs indicate greater flow and faster actuation.
The ANSI/NFPA standard rates flow in terms of Cv and most American and European companies express pneumatic-valve flow capability in terms of either Cv or Kv. Users in the American market have come to expect that all manufacturers test their valves in the same manner to produce Cv values that hold the same meaning-in essence comparing "apples to apples". Unfortunately this is not always the case. Some manufacturers do not use ANSI/NFPA or ISO 6358 to calculate Cv, and seriously overstate a valve's capabilities. Thus, it is critical to know the underlying method used to determine flow measurements.
JAPANESE STANDARDS
Some valve manufacturers publish Cvs that are calculated from the results of a completely different test - Japanese Industrial Standard (JIS) B8375-1981. The JIS standard tests for effective sectional area S, calculated in mm2, not Cv ( a dimensionless number).
Some manufacturers multiply the effective area by a constant to produce a supposedly equivalent Cv. The most common conversion is S=18.45Cv.
This is a critical flaw. Converting JIS test data into Cv results in flow ratings that exceed ANSI/NFPA or ISO values by 25 to 50%. As a result, manufacturers that use the JIS method publish flow ratings that substantially overstate actual performance. It is a bit like filling up at the gas station from a pump that reads 10 gallons but delivers only seven.
ANSI/NFPA methods also permit users to extract the actual data used to calculate Cv, such as flow, pressure drop, and time. This is not possible with the JIS conversion because it is not based on the original raw testing data.
Tests conducted in Parker's labs compared JIS-based performance data from several manufacturers' catalogs versus ratings on the same valves subjected to the ANSI/NFPA flow test. The actual results ranged from 20 to 35% less than the published Cvs.
Festo tested identical valves to ISO, ANSI/NFPA and JIS flow standards. The results, shown in the table, highlight substantial differences between the test methods. Unfortunately, a general error rate cannot be derived from this data, so a standard correction factor cannot be applied to JIS data to compensate for the overstated ratings.
Engineers aware of the potential discrepancies in Cv measurements usually try to compensate for the testing variance. But uninformed users who rely on published ratings will expect higher performance than the valve can actually deliver.
WORLD STANDARDIZATION
Until all manufacturers adhere to a global standard for flow testing, manufacturers of pneumatic equipment should make their customers aware of potential problems created by differences in flow measurements. System designers should require proper data from companies not following international standards.
Parker Hannifin, Festo, and Numatics are all firmly committed to international standards for rating pneumatic performance. Parker's position is that companies should publish Cv figures based on ANSI/NFPA or ISO standards, and not attempt to convert from other test methods.
Festo fully supports ISO 6358 as the proper basis for international standardization. The company also feels the standard should be expanded to encompass other valve data, switching time for example, where ISO and Japanese test methods also differ.
Numatics urges users who have test facilities to set up an ANSI/NFPA test rig to compare valve performance and determine true Cv ratings. While this entails time and expense, it is a prudent course to follow, particularly when purchasing large quantities of valves for applications that require precise timing and operate at maximum flow.
In the best interest of all valve customers, catalog data must be comparable. Therefore all important data needs to be based on commonly agreed international standards defining the test conditions. Otherwise users of pneumatic equipment may be misled and could draw inconsistent conclusions that lead to equipment malfunctions.