Power Requirements
115VAC @ .02A, 50/60Hz w/1000v magnetic isolation (I/O blocks are also available in 230vac or 12-24 vdc) Outputs 4 normally open relay contacts unprotected, no leakage current 5Amps @ 230VAC (resistive load), 250 VA (inductive load) Response time: 10ms operate / 5ms release Rated life: 5 million (mech) / 200,000 @ 3A (resistive load) Inputs 6 self powered, 12-14 VDC @ 10ma. w/ 1000v optical isolation Maximum leakage of input device: 0.5ma Response time: all are factory set at 10ms, the user may change any input to between 0 to 255ms using the Setup Physical Size 2.9" (75mm) x 2.2" (55mm) x 4.3" (110 mm) Mounting DIN rail or panel (with two #6 screws) Weight 10 oz. (284 grams) Temp 0 - 140° F, 90% r. humidity (no condensation) Origin Designed and assembled in the USA.